   Ampacity of
     Bus Duct
   Flexibility of
    Cable Tray

       Phone:
  859-635-4730

 


15000 Volts
COPPER CONDUCTOR CABLES



System
Number (1)
Nominal Ampacity (2) Conductor MCM Cables
Per Phase
Dimensions
H" X W" (3)
Wt.
Lbs./Ft.

CB15000C0350-03
CB15000C0550-03

CB15000C0750-03
CB15000C0500-06

CB15000C0500-06
CB00600C0750-06

CB15000C0750-09
CB15000C0750-09

CB15000C0500-12
CB15000C0750-12

CB15000C0500-18
CB15000C0750-18

CB15000C1000-18
CB15000C1250-18


400
600

800
1000

1200
1600

1800
2000

2500
3000

3500
4000

5000
6000

350
500

750
500

500
750

750
750

500
750

500
750

1000
1250

1
1

1
2

2
2

3
3

4
4

6
6

6
6

8 X 12
8 X 12

8 X 12
8 X 12

8 X 12
10 X 12

12 X 12
12 X 12

8 X 24
10 X 24

12 X 24
12 X 24

14 X 24 *
14 X 30 *

10
12

15
17

19
26

35
35

37
45

48
65

83
105

Notes:
(1)  Systems shown are three phase. Other systems available include three phase with neutral, single phase and D.C.
(2)  Based on ICEA Standard P-46-426 with conductor temperature of 90°C max. and 40°C ambient, other conductor and ambient temperature designs available.
(3)  Inside width, for overall width add 2" to inside width. * Check factory for fitting dimensions.
(4)  Aluminum Conductor Cable Bus is also available. (Click Here)



15000 Volts
ALUMINUM CONDUCTOR CABLES



System
Number (1)
Nominal Ampacity (2) Conductor MCM Cables
Per Phase
Dimensions
H" X W" (3)
Wt.
Lbs./Ft.

CB15000A0500-03
CB15000A1000-03

CB15000A0500-06
CB15000A0750-06

CB15000A1000-06
CB15000A1000-09

CB15000A0750-12
CB15000A0750-12

CB15000A1000-12
CB15000A0750-18

CB15000A1000-18
CB15000A1250-18

CB15000A1500-18
CB15000A2000-18


400
600

800
1000

1200
1600

1800
2000

2500
3000

3500
4000

5000
6000

500
1000

500
750

1000
1000

750
750

1000
750

1000
1250

1500
2000

1
1

2
2

2
3

4
4

4
6

6
6

6
6

8 X 12
8 X 12

8 X 12
8 X 12

10 X 12
12 X 12

8 X 24
8 X 24

10X 24
12 X 24

12 X 24
14 X 24 *

14 X 30 *
16 X 30 *

9
11

12
15

17
23

27
27

30
36

44
56

62
74

Notes:
(1)  Systems shown are three phase. Other systems available include three phase with neutral, single phase and D.C.
(2)  Based on ICEA Standard P-46-426 with conductor temperature of 90°C max. and 40°C ambient, other conductor and ambient temperature designs available.
(3)  Inside width, for overall width add 2" to inside width. * Check factory for fitting dimensions